Interface specifications
Rated voltage 12 to 48 VDC
Operating voltage 10 to 60 VDC
Rated current 250 mA @ 12 VDC
125 mA @ 24 VDC
63 mA @ 48 VDC
Rated frequency DC
Maximum inrush 0.3 A
2
s @ 48 VDC
current @ 10 ms
Polarity Reverse polarity protected
Redundant power input Yes
Isolation to All other 3 kV
rms
Connection Detachable screw terminal
Connector size 0.2 – 2.5 mm
2
(AWG 24 – 12)
Power
Electrical specification EIA RS-485
2-wire or 4-wire twisted pair
Data rate 300 bit/s – 115.2 kbit/s
Data format 7 or 8 data bits, Odd, even or none parity, 1 or 2 stop bits
Protocol Transparent, optimised by packing algorithm
Retiming Not applicable
Turn around time < 3 bits
Circuit type TNV-1
Transmission range ≤ 1200 m, depending on data rate and cable type (EIA RS-485)
Settings 120 Ω termination and fail-safe biasing 680 Ω
Protection Installation Fault Tolerant (up to ±60 V)
Isolation to Power 3 kV
Ethernet 1 1.5 k Vrms
Connection Detachable screw terminal
Connector size 0.2 – 2.5 mm
2
(AWG 24 – 12)
Shielded cable Not required, except when installed in Railway applications as
signalling and telecommunications apparatus and located
close to rails*
Conductive housing No
RS-422/485
* To minimise the risk of interference, a shielded cable is recommended when the cable is located inside 3 m
boundary to the rails and connected to this port.
The cable shield should be properly connected (360°) to an earthing point within 1 m from this port.
This earthing point should have a low impedance connection to the conductive enclosure of the apparatus
cabinet, or similar, where the unit is built-in. This conductive enclosure should be connected to the earthing
system of an installation and may be directly connected to the protective earth.